HomeMy WebLinkAboutTab D4 - Site Utility Study15150 N.W. 79" Court, Suite 200 Miami Lakes, FL 33016 T: 786.264.7200 F: 786.264.7201 To: Chris Gandolfo Swire Properties, Inc. From: Claudia Correa, P.E. Info: Hannah Lenard, Sherri Gutierrez (Arquitectonica), Leonardo Rodriguez (Langan) Date: 18 June 2018 Re: Utility Analysis Memorandum 650 South Miami Avenue and Associated Photo City of Miami, Florida Langan Project No.: 300229401 Langan Engineering and Environmental Services, Inc., has prepared this memorandum describing the utility infrastructure that will serve the proposed 650 South Miami Avenue and Associated Photo project. GENERAL The proposed 650 South Miami Avenue and Associated Photo Development ("the Project") is located in the City of Miami and is separated into two sites by South Miami Avenue (Southbound). The Associated Photo site is the smaller of the two sites and is bounded on the north by SW Miami Avenue Road and on the south by South Miami Avenue (Southbound). The larger site, 650 South Miami Avenue, is bounded on the north by South Miami Avenue (Southbound), on the east by South Miami Avenue (Northbound) and on the south by SW 7t" Street. The Project encompasses approximately 2.39 acres. The 650 South Miami Avenue site is planned to be developed with approximately 85,000 SF of retail and 550 residential units and the Associated Photo site is planned to be developed with approximately 400 residential units. The Associated Photo site as planned requires vacating SW 6th street. There are water mains, a gravity sewer main, a gas line, and power lines within the right of way that will require removal and relocation. See attached Appendix A Figure 2 depicting the relocation of the utilities along SW 6t" street. DOMESTIC AND FIRE SERVICES Miami -Dade Water and Sewer Department (MDWASD) will provide potable water and fire water services to the proposed site. See attached Appendix B for the letter of availability from MDWASD confirming the Department has sufficient potable water capacity to serve the project. MDWASD requires the relocation of the 12 -inch and 6 -inch water mains in SW 6t" street without disrupting existing services. Aside from the relocation of water mains, MDWASD did not request additional improvements to the surrounding water mains. Technical Utility Analysis Memorandum 650 South Miami Avenue and Associated Photo Memorandum City of Miami, Florida Langan Project No.: 300229401 18 June 2018- Paae 2 of 5 The 650 South Miami Avenue site will receive services on the south from the 12 -inch water main on SW 7" street and on the north from the relocated 12 -inch water main on South Miami Avenue (Southbound). The Associated Photo site will be served on the south by the 12 -inch relocated water main on South Miami Avenue (Southbound) and on the north by the relocated 12 -inch water main on SW Miami Avenue Road. See Appendix A Figure 1 for conceptual water and sanitary services plan. The fire hydrant flow test was conducted by the City of Miami Department of Fire -Rescue along SW 7" Street. Based on the results, there is adequate pressure and flow in the water main for the proposed development. No additional fire hydrant or water main improvements are required. See attached Appendix C for Fire Hydrant Flow test results. The fire hydrant located in the intersection of SW 6" Street and SW Miami Avenue Road will be relocated as part of the project. SANITARY SEWER Miami -Dade Water and Sewer Department (MDWASD) will provide sanitary sewer services to the Project. Please see Appendix B for letter of availability from MDWASD. MDWASD requires the relocation of the 12 -inch sanitary sewer main in SW 6th street without disrupting existing services. All the proposed buildings on the site shall connect to the abutting gravity sewers via service laterals. The 650 South Miami Avenue site will receive services on the south from the 12 -inch sanitary sewer main on SW 7th street and on the north from the relocated 12 -inch sanitary sewer main on South Miami Avenue (Southbound). The Associated Photo site will be served on the south by the 12 -inch relocated sanitary sewer main located on South Miami Avenue (Southbound) and on the north by the relocated 12 -inch sanitary sewer main on SW Miami Avenue Road. See Appendix A Figure 1 for conceptual water and sanitary services plan. The gravity sewer basin serving the project may not meet county criteria for conveying additional flows, including those proposed by the project. The sewer basin is currently undergoing improvements by MDWASD and will require a special connection fee from the developer to connect to the system. This fee will go towards the improvements of the general sewage conveyance system of the basin. GAS TECO Peoples Gas is the gas provider for the area of the project. TECO has confirmed that natural gas service is available in the project area. When the project is further along, TECO will require the service load calculations to provide detail plans of the underground service lines for the project. The gas line located on SW 6th street will require relocation for construction of the site. Please see attached availability letter provided by TECO in Appendix B. LAIVGAIV Technical Utility Analysis Memorandum 650 South Miami Avenue and Associated Photo Memorandum City of Miami, Florida Langan Project No.: 300229401 18 June 2018- Paae 3 of 5 TELECOMMUNICATION ATT is the telephone service utility for the general area. ATT has confirmed that service is available. When the project is further along, ATT will require more information to provide detail plans of services to the individual building of the project. Please see attached availability letter provided by ATT in Appendix B. Comcast is the internet communication service provider for the general area where the 650 South Miami Avenue and Associated Photo is located. Comcast has confirmed that internet communication is available to the serve the project. Please see attached availability letter provided by Comcast in Appendix B. POWER Florida Power and Light (FPL) is the electrical provider for the project area. FPL has confirmed that sufficient capacity is available to provide electrical services to the Project. The service will be provided in accordance with the applicable rates, rules and regulations. The transmission pole and lines located at the intersection of SW 6" street and SW Miami Avenue Road will require relocation before construction of the project. Please see Appendix B for availability letter from FPL. STORMWATER MANAGEMENT The project shall require a permit from the Miami -Dade County Department of Regulatory and Economic Resources (RER) Water Control Section. The water control section issues standard drainage permits for projects that encompass less than 2 acres and an Environmental Resource Permit (ERP) for projects that encompass more than 2 acres — because the project is divided into two sites by SW 6" street, the project will be permitted as two separate sites each under 2 acres. Therefore only a drainage report from the water control section is required. The drainage system for the project may consist of a combination of exfiltration trenches and drainage wells to fulfill storm water management requirements. The following criteria will apply to the project: • Site drainage shall be designed for a 5 -year 1 -hour event. • Stormwater quality to be 1 " over the entire site or 2.5" over the impervious area, whichever is greater. The 650 South Miami Avenue Site will require 5 wells and 300 feet of exfiltration trench and the Associated photo site will require 3 wells and 190 feet of exfiltration trench. See attached Appendix A Figure 3 for the conceptual storm drainage plan. The following assumptions were made in order to complete the preliminary stormwater management analysis: • Well discharge rate is assumed to be 500 gallons per minute per foot of head per well. • The percolation rate for the exfiltration trenches is assumed to be 1x10-5 cfs/sf-ft of head. This rate will have to be confirmed with percolation tests before beginning the detail design of the drainage a stormwater management system. LAIVGAIV Technical Memorandum Utility Analysis Memorandum 650 South Miami Avenue and Associated Photo City of Miami, Florida Langan Project No.: 300229401 18 June 2018- Paae 4 of 5 • A berm or retaining wall will be necessary at the property line along South Miami Avenue (southbound) and SW Miami Avenue Road ranging in height from .5 to 2.5 feet in order to meet the required county criteria for pressure head at the proposed stormwater wells at this location. FINISHED FLOOR ELEVATION The site is located within FEMA Flood Zone AE, which is defined as an area inside of the 100 - year floodplain. In accordance with Section 20-3 of the City of Miami Code of Ordinances, the minimum finished floor elevation (FFEL) shall be set by the higher of the following: • FEMA Base Flood Elevation +1 feet • Miami Dade County Flood Criteria Map +4 inches • Highest Adjacent Road Crown + 4 inches Basis of Base Flood Elevation Elevation (ft NGVD) Minimum FFE (ft NGVD) FEMA Base Flood Elevation 9 10 Miami -Dade County Flood Criteria 5.50 5.83 Highest Adjacent Road Crown ( SW 7th St.) 6.67 7.00 Highest Adjacent Road Crown ( SW Miami Ave Rd) 4.84 5.17 Highest Adjacent Road Crown ( S Miami Ave North Bound) 6.97 7.3 Highest Adjacent Road Crown ( S Miami Ave South Bound) 4.84 5.17 Based on flood criteria the minimum FFE for the proposed buildings shall be 10 feet (NGVD). The adjacent road crown elevations shown above are ranges based on limited available information shown on the surveys from Fortin, Leavy, Skiles, Inc. dated March 13th, 2018 and supplemental information from Google Earth software. Attachments: Appendix A Figure 1: Conceptual Water and Sanitary Sewer Services Figure 2: Conceptual Utility Relocation Plan Figure 3: Conceptual Storm Drainage Plan Appendix B MDWASD Letter of Availability 12 June 2018 TECO Availability Letter 06 April 2018 ATT Availability Letter 1 May 2018 Comcast Availability Letter 19 April 2018 FPL Availability Letter 18 June 2018 Appendix C Fire Hydrant Flow Test LANGAN Technical Utility Analysis Memorandum 650 South Miami Avenue and Associated Photo Memorandum City of Miami, Florida Langan Project No.: 300229401 18 June 2018- Paae 5 of 5 Cc: Chris Gandolfo, Hannah Lenard, Sherri Gutierrez (Arquitectonica), Leonardo Rodriguez (Langan) FL Certificate of Authorization No. 6601 LAIVGAIV APPENDIX A 2 3 4 II s 6 7 s ASSOCIATED PHOTO SITE— .;;, N SW 6TH ST RIGHT OF WAV TO BE VACATED RELOCATED 12" SANITARY SEINE PROPOSED 80 0 40 80 RELOCATED 12" WATER MAI RESIDENTIAL RELOCATED 6" WATER MN BUILDING / I SCALE IN FEET � I PROPOSED SERVICE J PROPOSED DOMESTIC WATER SERVICE BUILDING �/ ROPOSED SANITARY " SEWER LATERAL PROPOSED FIRE SERVICE SEROPOOSEED DOMESTIC WATER II \ PROPOSED SANITARY SEWEROPOSED FIRE ROPOSED FIRE SERVICE SERVICE TQC` W ROPOSED SANITARY SEWER LATERAL ROPOSED SE DOMESTICWATER SERVICE 1� I PROPOSED I RETAIL .01 BUILDING II III I 0 PROPOS D I RESIDE IAL 50 SOUTH MIAMI AVENUE SITE PROPOSE v BUILD I G SERVICE D I i� BUILDING "SVV 7Ti ST �-D DOMESTIC WATER SERVICE PROPOSED DOMESTIC WATER SERVICE PROPOSED FIRE SERVICE PROPOSED FIRE SERVICE PROPOSED SANITARY SEINE PROPOSED SANITARY SEWE PROPOSELATERAL E I I P a, Drawing TO FroF3 No. Drawing No. LANGAN 650 SOUTH MIAMI CONCEPTUAL Da ^3oozz9aol Lanean enemeedns aad m, AVENUE AND WATER AND 06/07/2018 FG 1 16160 Nw19lh Cmu Suile20° ASSOCIATED PHOTO Draw ay MizmlLA. FL 33016 SANITARY SERVICES JMA T 166.264.7200 F'. 786.264.7201 .v:mvv.langaacom MIAMI Cneckea By FLcena�calemnmeori�alior No.000a660LLB817vLBa196 MIDADE FL AMF PLAN erne Filename'.\\langan.com\data\MIA\data4\388229481\Project Data\CAD\01\SheetFlles\Figures\FG01-388229481-CU101-0102.dwg Date'. 6/18/2818 Tlm,'. 11'. 20 User'. jaquino Style Table'. Langan.stb Layout'. SERVICES 2 3 4 5 6 7 B s N it a I� i FPL TRANSMISSION LINE RELOCATION REQUIRED �y 40 0 10 25 40 FPL TRANSMISSION POLE ,� S F SCALE IN FEET RELOCATION REQUIRED RELOCATED 12"SANITARY SEWE / ®� S a RELOCATED 3" GAS MAI RELOCATED 12" WATER MAIPROPOSED / 5 RESIDENTIAL FPL TRANSMISSION LINE RELOCATION REQUIRE < BUILDING 5 / RELOCATED 6" WATER MAI oww a � KKvv"" r u, rm w O //% :,a , ,i�unrrunruw "' ,iwpn('h'uri r nnarnl,u, O _ _w'" —w_w r rrrrrr ���III s —s—s—� s �� rig a ,;� LEGEND rrrr, ..S G nvr a ri"rrJl.;,,r, rr w IN � w w urro, � RELOCATED WATER MAIN -UW EXISTING WATER MAIN /J RELOCATED SANITARY SEWER • PROPOSED SERVICE EXISTING SANITARY SEWER —s s— BUILDING ���/// J � RELOCATED GAS MAIN uD F 4 EXISTING GAS MAIN c V D � DEMOLITION LINE 01 EProject Drawing Title Fropcl No. Drawing No. LANGAN 9"k SOUTH MIAMI 30D229401 Lang.n engmeerms.ad CONCEPTUAL �01/1r.7/101 AVENUE AND s15160NW791hC,,a Sulie20° ASSOCIATED PHOTO UTILITY ay FG 2,Ifi—LA. FL33016RELOCATION PLANOMAT786.264.7200 F 786.264.7201 u�wwI"I'"MIAMILLaaise MIAMI-DADE FILrne Filename'.\\l.ng.,..o \data\MIA\d.t.4\300229401\Project Det.\CAD\01\SheetFllee\Figures\FG01-300229401-CU101-0101. dwg D.te'. 6/18/2018 Ti— 11'.16 Ueer.j.q—. Style Table'. L.ng.n.etb Layout'. UTILITY RELOCATION PLAN B ASSOCIATED PHOTO SITE 4 N 80 0 40 80 SCALE IN FEET LEGEND PROPOSED WELL B PROPOSED EXFILTRATION TRENCH PROPOSED YARD DRAIN • STORMWATER DRAINAGE REQUIREMENTS DRAINAGE AREA DRAINAGE AREA (Ac) No. OF WELLS LENGTH OF EXFILTRATION TRENCH (FT) 650 SOUTH MIAMI AVENUE SITE 1.66 5.0 300 ASSOCIATED PHOTO SITE 0.73 3.0 190 Total 2.39 8.0 490 50 SOUTH MIAMI AVENUE SITE Filen.. e'.\\lang,n.c om\data\MIA\d,ta4\300229401\Project Data\CAD\01\SheetFl l es\Figures\FG01-300229401-CG102-0101. dwg Date'. 6/18/2018 Ti- 13'.20 User'. jaquinc Style Tabl,'. Langan.stb Layout'. STORM APPENDIX B MIAM I•DADE m is m idade.gov June 11, 2018 Swire Properties, Inc. 98 S.E. 7 Street, Suite 601 Miami, FL 33131 Water and Sewer P© Box 330316 • 3071 5W 38 Avenue Miami, Florida 33233-0316 T 305-665-7471 Re: Water and Sewer Availability for (18-361901) for "650 South Miami Avenue & Associated Photo", construction and connection of 85,000 sq -ft of retail and 950 apartments, generally bounded north by S,W. Miami Avenue Road, east by South Miami Avenue, and south by S.W. 7 Street, Miami, Florida, Folios #01-0200-010-1040 & 01-0200-010-1070, and 01-0205-030-1140, 01-0205-030- 1150, 01-0205-030-1160, 01-0205-030-1040, 01-0205-030-1010, 01-0205-030-1170, 01-0205- 030-1120, 01-0205-030-1180, & 01-0205-030-1130, and 01-4138-070-0020 & 01-4138-070-0010. Ladies and Gentlemen: This letter is in response to your inquiry regarding water and sewer availability to the above -referenced property for the construction and connection of eighty-five thousand (85,000) square feet of retail and nine hundred fifty (950) apartments. According to Miami -Dade County G.I.S., this property is a Department water customer. Therefore, if a new connection is necessary, the developer shall connect to any of the followings: 1. An existing twelve (12) -inch water main (E 14310.7) in S.W. 7 Street, abutting the southern boundary of the subject property. 2. An existing twelve (12) -inch water main (E 817-1) in South Miami Avenue, abutting the eastern boundary of the subject property. 3. An existing twelve (12) -inch water main (E 817-1) in S.W. 6 Street, within the proposed area of development. If the Fire Department requires a fire hydrant, a fire line, and/or the developer requires service in S.W. 1 Avenue, thence the developer shall connect to the aforementioned existing twelve (12) inch water main in S.W. 1 Avenue west of South Miami Avenue and extend the same (12) inch water main southwesterly in S.W. 1 Avenue as required to feed the hydrant, fire line, and/or provide service to the property. If the Fire Department requires a fire hydrant, a fire line, and/or the developer requires service in S.W. Miami Avenue Road, thence the developer shall connect to the aforementioned existing twelve (12) inch water main in S.W. 6 Street at S.W. Miami Avenue Road and extend the same (12) inch water main northeasterly in S.W. Miami Avenue Road as required to feed the hydrant, fire line, and/or provide service to the property, interconnecting to an existing six (6) -inch water main (E 7729-1) at that location. Any public water main extension within the property shall be twelve (12) -inch minimum diameter. If two (2) or more fire hydrants and/or fire lines are to be connected to a public water main, then the water system shall be looped with two (2) P.O.C. According to Miami -Dade County G.I.S., this property is a Department sewer customer. As ;per the engineer's concept connection plan, the developer may connect as follows: 1. An existing eight (8) -inch gravity sewer (ES 2850-1) in South Miami Avenue, abutting the eastern boundary of the subject property. 2. An existing twenty-four (24) -inch gravity sewer (ES 8614-3) in S.W. Miami Avenue Road, abutting the northwestern boundary of the subject property. If unity of title does not apply, then any gravity sewer within the property shall be public and eight (8) - inch minimum diameter. The County hereby represents and the developer acknowledges that the gravity sewer basin that will serve the developer's property, at the present time may not meet County criteria for conveying additional flows, including those of the proposed development within the developer's property as specified above. The County intends to construct the necessary improvements, and has adopted a special connection charge to pay for the construction of necessary improvements in accordance with County Ordinance No. 12-36. The developer acknowledges and agrees that it shall pay to the County said special connection charge in the amount of three dollars and ninety cents ($3.90) per average daily gallon for the proposed development to be connected to the County's sewer system, due prior to the issuance of a Verification Form. Said payment shall be a condition precedent to any obligation on the part of the County to provide service to the property. Per the engineer's concept site plan, part of S.W. 6 Street is proposed to be vacated. There are water and gravity sewer mains within the property, either in existing dedicated right-of-ways or easements, which need to be removed and relocated if in conflict with the proposed development. Easements associated with mains to be removed and relocated shall be closed and vacated before starting construction in the easement areas. In case of right-of-ways to be closed and vacated within the property, mains shall be removed and relocated, if needed, before closing/vacating them. Fire hydrants associated with mains to be removed and relocated shall be relocated as per Fire Department recommendations. Cutting and plugging of existing water and gravity sewer mains shall be done by the Department's forces at owner's expense. Services to existing customers cannot be interrupted. Construction connection charges and connection charges shall be determined once the developer enters into an agreement for water and sewer service, provided the Department is able to offer those services at the time of the developer's request. Information concerning the estimated cost of facilities must be obtained from a consulting engineer. All costs of engineering and construction will be the responsibility of the developer. Easements must be provided covering any on-site facilities that will be owned and operated by the Department. Please be advised that the right to connect the referenced property to the Department's sewer system is subject to the terms, covenants and conditions set forth in court orders, judgments, consent orders, consent decrees and the like entered into between the County and the United States, the State of Florida and/or any other governmental entity, including but not limited to, the Consent Decree entered on April 9, 2014, in the United States of America State of Florida and State of Florida Department of Environmental Protectiony. Miami -Dade„ Count , Case No. 1:12-cv-24400-FAM, as well as all other current, subsequent or future enforcement and regulatory actions and proceedings. Water and Sewer LOA (18-361901) The purpose of this LOA is to confirm water availability/capacity and that there is capacity at the receiving sanitary sewer pump station at this time. Therefore, no gravity sewer capacity analysis was performed. At the time this project applies for an agreement, the necessary analysis will be performed. Please be advised that upgrades to the sewer system might be required depending on the results of the analysis. This letter is for informational purposes only and conditions remain in effect for thirty (30) days from the date of this letter. Nothing contained in this letter provides the developer with any vested rights to receive water and/or sewer service. The availability of water and/or sewer service is subject to the approval of all applicable governmental agencies having jurisdiction over these matters. When development plans for the subject property are finalized, and upon the developer's request, we will be pleased to prepare an agreement for service, provided the Department is able to offer those services at the time of the developer's request. The agreement will detail requirements for off-site and on-site facilities, if any, points of connection, connection charges, capacity reservation and all other terms and conditions necessary for service in accordance with the Department's rules and regulations. If we can be of further assistance in this matter, please contact us. Very truly yours, Douglas Rile, sq. New Business Contracting Officer Water and Sewer LOA (18-361901) AN EMERA COMPANY Gabriela Silva 5101 NW 21St Avenue #460 Fort Lauderdale, FL. 33309 305-297-4763 April 4t", 2018 Attn: Julissa Aquino LAGAN Re: Folio Number 01-0205-030-1170 640 S Miami Ave Miami, Fl 33130 To Whom It May Concern, TECO Peoples Gas has natural gas service available in the vicinity of the above- mentioned property and we welcome the opportunity to service your client with natural gas. Feasibility and capacity for installing the underground service to the above referenced location can be determined once we have the required load calculations and site plan with proposed meter locations. Please call if you have any questions. I can be reached at 305-297-4763. Regards, Gabriela Silva Account Manager 305-297-4763 at&t Service Availability Letter May 1st, 2018 Claudia Correa Langan Engineering & Environmental Services, Inc. 15150 NW 791h Court Suite #200 Miami Lakes, FL 33016 RE: New Development located in proximity of 650 S Miami Av, MIAMI, FL 33130 Dear Claudio Correa: This letter is in response to your request for information on the availability of service at the above referenced property, by BellSouth Telecommunications, LLC d/b/a AT&T Florida. This letter acknowledges that the above referenced property at 650 S Miami Av, is located in an area served by AT&T. Any service arrangements for the project will be subject to later discussions and agreements between the developer and AT&T. Please be advised that this letter is not a commitment by AT&T to provide service to the properties. Please contact me at the phone number included in this letter with any questions. Thank you for contacting AT&T. Sincerely: Michael Parr01- MGR OPS PLNG & DESIGN SE/CA AT&T Florida T: 305-222-8734 Email: MP0471 @ATT.COM 9101 5W 24111 St, Miami, Florida 33165 Ift COMCAST Engineering - Design Department 2601 SI 145" Ave Miramar, F133027 Thursday, April 19, 2018 Julissa Aquino Langan 15150 NW. 79 Court, Suite 200 Miami Lakes, FL 33016 RE: Comcast Serviceability Conformation Request Project Name: 650 South Miami Avenue Project Location / Address: 650 South Miami Avenue. Miami, FL 33130 Dade County Folio Number: Dear Ms. Aquino 01-0200-010-1070, 01-0200-010-1040 01-0205-030-1120, 01-0205-030-1130 01-0205-030-1140, 01-0205-030-1150 01-0205-030-1160, 01-0205-030-1170 01-0250-030-1180, 01-0205-030-1010 01-4138-070-0010, 01-4138-070-0020 01-0205-030-1040 Please be advised, in reference to your proposed project: 650 South Miami Avenue located between SW 1 Ave to the West, SE 5 Street to the North, S. Miami Ave to the East and SW 7 Street to the South, Miami FL 33130 ... will be located within a Comcast Service Area. Please Note: Comcast has the capacity to provide our services to your planned Residential property. For further information on the provision of service to this location, please contact our Business Development Department. Margaret Hutter Comcast Business Development Ph. (954) 514-8310 Should you have any further question, please feel free to call me at 1-954-447-8405 fax 1-954-447-8445 or e-mail at Leonard Maxwell-Newboldgcable.comcast.com Sincerely, Leonard Maxwell -Newbold Tech 3 Network Engineering Regional Permit Manager Comcast / Southern Division (RDC) 4/19/2018 10:53:28 AM cc: Julissa Aquino - Langan Margaret Hutter - Comcast Business Development Ric Davidson - Comcast Construction Supervisor (South Florida Region) 0 FPL June 18, 2018 LANGAN, LLC Claudia Correa, PE 15150 NW 79" CT Miami Lakes, FL 33016 Re: Electric Service Availability 650 S Miami Ave, Miami. FL 33130 Dear Claudia, Florida Power & Light Company I am familiar with the subject properties and hereby advise you that Florida Power & Light Company is prepared to supply all necessary and required power to the referenced properties. FPL currently has existing facilities in the vicinity of the site which will supply the power requirements, with the understanding that the owners will grant to Florida Power & Light Company any other easement rights necessary to provide the service from existing utility easements to the property; and pay, if required, any overhead to underground differential costs. Power will be supplied at prevailing rates for the appropriate class of service. Prior to beginning construction of the above referenced property, FPL will need certain information in order to design the electrical facilities needed to provide electric service. It is a pleasure to be of service to you. Thank you for your cooperation and if I may be of further assistance, please call me at (305) 377 - 6106. Sincerely, Adrian Arroyo, Associate Engineer Central Dade Service Center an FPL Group Company APPENDIX C • }City of 1ami Fire Flow Test Request „\%\%.mtamlgov.com Water Supply Officer 444 SW 2 Ave. # 441 / Miami, FL 331301 Ph: 305-416-1679 Name of Applicant Claudia Correa 15150 NW 79th Ct. Suite 200 Business Address Miami Lakes, FL 33016 Company Contact Number (786) 264-7265 Email Address ccorreaC@langan.com Fax Number Would you like the results to be sent by email? Yes X No Project Address 650 South Miami Avenue This is a request for: New Structure / Addition to existing structure / draulic Calculations please circle answer) Property is zoned Rapid Transit - High Density Number of Stories Varies Proposed height (feet.) Varies Proposed Use of Building Retail/Residential Is sprinkler system being installed? Yes X No Sq. footage per floor Varies Total Sq. Footage 85,000 Is standpipe system being installed? Yes X No Building Construction Type: Type I A fee of $250.00 is due upon submittal of the Fire Flow Request. Flow Test Number: 6111 (Page 1 of 2) Please also attach: *Site Plan *Location Sketch (/ 1,5 Date _1t of Miami i if glow Test Request pg.2 wivw mlamlgov.cvm Water Supply Officer 444 SW 2 Ave. 4 441 / Miami, FL 33130 / Ph: 305-416-1679 Street Index Page : Zoning Atlas Page: 'PH) Required Flow: The above application is: Approved for a foundation permit only. Approved — Compiles with NFPA Standards. Disapproved — Does not comply with NFPA Standards. Hydrant Installation(s) required Yes No Water Main Improvements Required Yes No Flow Test Number: War S pply Officer glum Date PLANS HAVE BEEN PROCESSED AND APPROVED L NECESSARY AGENCIES ND A BUILDING PERMIT IS NOW APPROVED ON THIS TE: WATER SUPPLY OFFICER IN FIRE HYDRANT(S) INSTA ION ONLY. DOCUMENTATION HAS BEEN PROV DED HA HYDRANT INSTALL N HAS BEEN PAID FOR IN ADVANCE. A BUILDING PER IS NOW APPROVED: DATE: WATER. SUPPLY OFFICER CONTACT #305416-1679 (Page 2 of 2) Document Name: FIRECADPROD01 Date: 4/19/2018 Time: 9:08:11 AM MFD HYDRANTS - REVIEW (INQUIRE) A SYSTEM FLOW TEST SITE ADDRESS: 650 SOUTH MIAMI AVE SYSTEM TEST NUMBER: 6117 INDEX PAGE: 0 RECORDED BY BADGE NO: 1402 ZONE: FERNANDEZ JOSELIN FLOW REQUIRED: 1000 / 3000 ATLAS PAGE: F14D TIME: 800 TOTAL TEST DISCHARGE: 2078 DATE: 04/19/18 AVAILABLE GPM AT 20 PSI: 10476 STATIC HYDRANT NUMBER: 5656 LOCATION: SW 7 ST & S MIAMI AVE - SW CORNER STATIC PSI: 60 RESIDUAL PSI: 58 MAIN SIZE: 12.0 FLOW HYDRANTS: OUTLET NUMBER LOCATION PSI DIAM GPM 5538 SW 7 ST E OF SW 1 AV S SIDE 34 4.0 2078 0 0 0.0 0 0 0 0.0 0 0 0 0.0 0 0 0 0.0 0 SELECT ACTION: 1- CONTINUE 9- MENU ACTION: 1 Date: 4/19/2018 Time: 9:08:11 AM 6TH ST--, P SW 7TH ST -'�41 T*j SE 7-M ST cn r'h. 24"