Occupant Loads
The purpose of the occupant Toad is to reflect the maximum number of people anticipated to occupy
building rooms or spaces at any given time and under all probable situations.
• An occupant load is established for use in sizing the means of egress system and in determining
thresholds at which additional provisions, such as mandatory sprinklers, become applicable.
Calculating an Occupant Load
Calculating an occupant Toad of a space consists of acquiring either the net or gross area of the space
and dividing it by the occupant load factor listed below in Table 7.3.1.2 assigned to the use. If a space
has multiple uses (i.e. kitchen and dining area), then each area shall be calculated using the appropriate
occupant load factor assigned to that use in determining the occupant Toad.
Occupant Load Certificate
An Occupant Load Certificate is required in every room constituting an assembly occupancy and not
having fixed seats. This is to assist in avoiding overcrowding.
• The sign shall be posted in a conspicuous location near the main exit from the room.
• An assembly occupancy is an occupancy used for a gathering of 50 or more persons for
deliberation, worship, entertainment, eating, drinking, amusement, awaiting transportation, or
similar uses.
Establishments that exceed their occupancy load put the public in danger and can lead to
delays or the inability of occupants to exit an establishment during an emergency.
Crowd managers are required in assembly occupancies and must possess a current training
certificate from an approved provider, which has been issued in the last two years. Training is
required consisting of understanding crowd management techniques, evaluating projected
levels of occupancy and the adequacy of means of ingress and egress, methods of evacuation
and movement, procedures for reporting emergencies, understanding safety and security
hazards that can endanger public assembly, etc.
12.7l3 Occcspaat Load Piestia _
12.7L3.1 eery room constituting an assembly occupancy and
not hates fixed seats shall hair the occupant led of the room
posted in a conspicuous place near the maim exit from the room
12.71.31 Approved signs shall be 1111intRiBEC1 m a legible maanor
by the owner or authorized agent
12.7JJJ Signs shall be durable and shall indicate the number of
occupants petmimed for each room use_
9389 Subm-ffaJ-&hMe'-ntyu-5&ku-p
Submitted into the public
record for item(s) 01.4
on `r 22 ML1, City Clerk
7/20/21
MEANS OF EGRESS
7.213.f= Water Pratectioa. Bwlctne elements shall be used to
Mahn water exposure of =2.evater egn:pment
7.213.7t Power and Coatrol Wiring.. Elevator equnornent.
devater cotramlicatens. elevator mach-ne room tooii and
elevator controller .vain- shall be suppiiied by both normal and
standby power Wirt for power and control shall be located and
properly prorec ed to ensure a minimum 1 hour of operation in the
event ale fire
7.213.S* Communications. Two-way comunrnrrinon s+stems
shall be provided between elevator lobbies and 3 central connol
point sad between elevator cars and a cenae! control pone.
Commuincanons wring shall be protected to ensue a mtremWa '
hour of operation in the ei:enr of ere
7 213_9* Elevator Operation Elevators shall be provided with
fire fighters' emergency opera:Ions in accordance with ASI4E
A17.1.CS,A E44.. St jer} Cade for c`iat rtor: grid E:calaaor:.
7113_10 Manteasace_ Where an elevator lobby is served by
only one eietator car, the elevator evacuation system still have a
program of scheduled maintensosce during tares of budding
shutdown or low building activity. Repairs shad: be performed
w=haa 24 bass of breakdown
7_2.13_11 Earthquake Protection_ Elevators shalt have the
capability of orderly shutdowns during earthquakes at Locations
where such shutdowns are an option of ASME A17 I CS.A B44.
500 Code for E: errors and E.xer&ror:.
7_21312 Stooge_ Stgna*e shall comply with `. lc., 3 4.
13 Capecits of 3lman of Egress_
7.31 Occappaat Load.
7.311 Suariear Capacity.
13111 The total capacity of the memos of egress for any story,
btdcon!r, tier. or other occupied space shall be sufficient for the
occupant load thereof.
7.1_11_1 For other than enthral.; means of egress. where more
than toe mesas of egress is required. the means of eetess shall be
of such wda and capacity that the loss of stay one means of
egress leaves at•auable not less than 50 percemt of the required
capacity
7.3.11' Occupant Load Factor_ The ocrupanr load an nay
budding or portion thereof ;hall be not less than the number of
persons determined oy dividing the floor area assigned to that lase
by the occupant road factor for that use as speczned ma Table
'.3.1 Figure 7.3 ; _ .3_, apt r:p.tre , Where both
gross and net area 5gmes are grata for the same occupancy,
calculations shalt be made by applying the gross area true to the
grass area of the portion of the building devoted to the nine fca
which the gross area 7g7re is specified mad by applying the net
area 5.gure to the net area of the portion elite building denoted to
the use for which the net area aeure is specified_
73.13 Occapiat Load increases.
7.3.1J' _1 The occupant load ii airy budding or portion thereof
shall be permitted to be increased from the occupant load
established for the v*.en use in is orsiance with 3 1.'_ where ail
other regarrenaeats of this Coda are also :stet, based on oath
increased accupantload.
Table 7.3.1.2 Occapata Load Factor
Use
A.sembly tise
Coated,
without 5: e: seamg
Less catceoaated use
Indian fixed
seating
Bench-ryPe wag
Faced Eearpg
r'I-a"1r'P macei
:Zorn . stack areas
reading maws
Sw=g Nob.
Swimming pool
Esecrse rotors wt&
equgsruxa
Exert is roosts
without eSst?ment
Stages
Lighticg and aces
cataraieaiitnes,
gridiron
l"15mos and ;i:.n:tar
thrinag wee
Strong nr1;
Restates Use (Winer
duo below
Ccmcenratec
S:istness Ir se
Alt anffic cannot
tower obser anon
Les�`s
Da* -Care Ux
Detredeta and
C err: ec tioasl
Edict aortal I -se
C ESTOeL:i
ncs..*torotors:.
vocanoA1. looms
Health C are Use
4ust neatmem
deparunem
Seeping departments
Ambu atnnt's health
use
Industrial [ se
General and high
iniatvial
Spectal•parpose
incEntrtal
Mercantile Use
SAYS area do street.
floe'
Sales area on two or
here street avers'
Sales area or door
below stilt Eon -
person)' (m•per oa)'
7net
15 net
1 person
III=.
Use anther of
fixed seats
See 121':and
131'_
100
100
50 net
50 €1wa1S tfa-e)
30
50
15
li net
100 net
11
50
1Cd
50
Hie
1.10
20 set
50 net
240
120
150
100
NA
30
0 3 lei
1 4 net
1 perwn
a..5 :meat
sett::.
Use theater of
Erred seats
See12.L'' ar►i
13.I."
9.3
9.3
4.11 art
4.0(inferwbee)
21
4.6
1.4
1.4 Wt
93 nee
4.ti
43
+.5
3
1.9 net
4l1 net
93
3.7
21
Submitted into the public
record for item(s) 171.'di
on 71Z224221, City Clerk
101-76
LIFE SAFETY CODE
7/20/21
Tah1e 7.3.12
(iir:persear (caltpersoar
Sales aria on floors above
saran
Roar: or portions o`
floors used melt for
Maces
Foots ar portions of
floor used only par
sump. recaninv
mad Jarppin-=. ,marl cot
Cp211 to ztacer1l
Mil hnidirte;'
Re adeanal Use
lost:s art dorssacces
buildmp
Baud and cr^e.:arge
Storer ['se
In storage occxparuies
metriconle accnpaotis
:a other dun storage and
mercantile
occupancies
so 5.6
See'bumaess use. Set business me..
30,3 d'.9
lrytS' r.1Caa3
apphcable'a use
of space
206
;Oral
200
500
NA. Not applicable. The occupant load i; the toasimuum probab:e a tar.` a
of octhpazis present a aes pine.
Sctt>r a_rz amprsec in uoss area viols rt_alu>•d -'nor."
'For the 7-or-pose of detei in z_ occupant ;oad la mertiri.0 a a.^.taactes
Mute. Mt to er:cc in the rushed ground :evei streets oa:
i5��ct sides. two or mare Emote dicKtly acressibie from Mori (cot
uchair97 z~n s ar t r ular back smuts) man. each ;ark foot is permitted
to be can:_: red a Ilea f_.aor. The occupant mad .rtor 15 one bog
each -k f1 ' re; of pose floor area of saiti space.
'Fir the ptmpose of determining xrtpmr load in inert,: r£°e or-ipanmes
with no street Boor, as tuned is ::' 1, hit gait access 'ten rs _
the street br stairs or escalators, the floor at the ;cant of entrance to the
=manta (!ccusaray is considered the street floor
'Fa cry food court or odic assem'vi1• are anus :anted as the =2 That are
rot included as a portion. of the goes; :easab:e area of the alai buil:hag.
the occmanr 'cal calculated based on the occupant :awd'rcta for Scat
use as sae ified is : i:':e - _ .: _. The rismuning mad area is not TNa3red
ro be assigned an occupant load.
'The portions of tie mall that are considered a pkesman wry and not
•teed as ass :eatable area are mot :gutted to be assessed a. occupant
:cad based a Ts; is " , 1 L However toms of tress Sac a traL
pedestrian wax are respired to be provided for an outman: load
determined by dividing the gess leasabie zee of the tnaw: bsn;dirg ,mot
me:udty; anchor cares) err dies appropriate lowest whore racibec oc_ rpm .r
toad fat tall' tom i._,rre ' 3 1 ;a) or . 7 €'_;.
Earl mdtstncAl tenant space is rego:red to Sage means of s=ass to the
oat.ide or to rise 1raa.T based on oc..W>ant t i rr-,wed i+ mica the
appropriate ocnipanz'mad Attu once
Each ir.d virtu: aecfix ware is maimed to hive means of ogees
mdepentle t of the mail.
'See A. - _ .._.
100 rya 20' 291 360 360 400 4,50
GrcaEirasa6Marms lf° 1t]Y31
FIGURE 73.12(a) him[ Banding Occupant Load Fartuu,
(U.S. Customary Units).
uq.
a3MMrlari.Owen* rma
MM MMrMMrwn BIM
RI MO MMMMM MOM
BIM MO MMMMMM me
rRMEMI arM essaar a
coon ��
rrrcMMM
81021 sal pry ma reit
ORM10 UM* e>ea (re° x 1001..
F'IGI.Titt 7:3.11(b) Man Building Occupant Load Factors (SI
Units).
7.3.1) 2 The aMrlacity laamag Jurisdiction shah be permuted to
revue au approved aisle, seating. or fixed equipment diagam to
siabsmntiate my increase in occupant load and shalt be permuted
to require that such a diagram be posted an as approved location.
7314 Exits Serving Bore than Orr Story. Where an east
sett -es more than ace storyonly the occupant load of each sway
considered individually droll be used in compurmg the required
capacity oldie emir at that start, provided that the retlarred Gress
capacity of the emit is not decreased in the direction of egress
73.1.5 Capacity from a Point of C owver1ence. Who =tams of
eaess from a story aba,.e and a story below converse at an
inrermednte story, the caparr-v of the mans of egress from the
point of convergence shall be not less than the sum of the requaed
capacity of the two means of egess.
Submitted into the public
record for item(s) DI 4
on 7'/22/Lo21, City Clerk
7/20/21
Process of Acquiring an Occupant Load Certificate
Instructions regarding acquiring an Occupant Load Certificate are available on the City of Miami website.
Customers will find these instructions by either entering key words, such as "occupant load" into the
search bar or can also find this information when acquiring step-by-step instructions when seeking to
apply for a certificate of use.
The customer will be asked to submit basic information, such as business name, address, CU number,
and contact information. Additional directions are included on the site pertaining to how to submit
plans electronically and how to access ePlan.
Once the plans are uploaded, the Fire Marshal's Office reviews the plans and visits the
establishment to verify the plans are accurate. The Fire Marshal's Office then provides a signed
Occupant Load Certificate communicating the maximum occupant load for the space, which the
customer can download along with the approved plans on ProjectDox,
Electronic Plans Review
The Fire Prevention Bureau has migrated to issuing occupant Toad certificates using the same electronic
plans review platform that is used in the City of Miami permitting process. This was implemented to be
consistent with other city departments, allow for easy retrieval of past occupant load certificates and
plans, and to provide an improved means for customers to submit plans at any time.
• In the past, floor plans and drawings utilized in determining occupant loads were stored as hard
copies, which consumed space and were difficult to locate.
• Customers are provided with detailed instructions regarding the process in acquiring an
occupant load certificate. These instructions are also located on the City of Miami website and.
also accessible via search function. An example of the instructions presented on the City of
Miami website are included at the end of this document.
Current Actions to Assure Compliance with Occupant Loads and Occupant Load Certificates
• A public service announcement is in the process of being developed, which communicates the
requirement of an occupant load certificate, the importance of assuring maximum occupant
loads are not exceeded, and instructions regarding how to acquire a new or revised occupant
load certificate.
• The Fire Prevention Bureau has been compiling past hard copy occupant load certificates along
with all occupant Toads submitted via electronic plans review. Additionally, fire inspectors are
visiting assembly occupancies to verify that occupant load certificates are posted, as well as
taking photos of them for our records. The goal is to have all maximum occupant loads that are
communicated on occupant load certificates easily accessible.
Submitted into the public
record for item(s) Di. 4-
on 7/224202-1 , City Clerk
7/20/21
• Establishments who have lost their occupant load certificate(s) are provided instructions
regarding how to acquire a new occupant load certificate. For those occupancies not working to
acquire an occupant Toad certificate in a timely manner, a conservative temporary occupant
Toad certificate will be provided,
• Fire inspectors are visiting assembly establishments during the day and night to ensure
maximum occupant loads are being adhered to and will be taking appropriate action
when needed.
Certificates of Use: Active Assemblies with
occupant loads over 200 (Restaurants over 3,000
sqft, all Taverns, all Nightclubs).
Additional
Found
Total
Inside
42
12
54
Inside/Outside
10
4
14
Get an Occupant Load Certificate
Do you own a place of assembly (restaurant, bar, club, etc.) that hosts more than 5
people in one room, and need an Occupant/Occupancy Load Certificate? If you are
opening a new business, renovating a business, changing a business name, and/or
applying for a Certif cate of Use, you will not pass your fire inspection without this
certificate if applicable. Occupant loads are required for all interior assembly areas and
enclosed exterior assembly areas.
NOTE If you have been operating without an Occupancy Load Certificate, you will receive
a violation and need to complete this process. Once you complete this process, your
violation will be removed.
Every room constituting an assembly occupancy. and not having fixed seats shall have the occupant
Icad of the room postec in a conspicuous place near The main exit from. (Florida Fire Prevention Code
1.20.1.5.10.4).
View the Florida Fire Prevention Code LgIviaer 6} for a definition of what constitutes an assembly
cccupancy.
68
Contact Us
Phone
305-415-1544
Email
fph@miamigov.com
Location
Miami
Submitted into the public
record for item(s) DI 4-
on 7/22/2b21, City Clerk
STEPS
Collect Documents
n order to apply for your Occupant Load Certificate, you will need:
• A floor plan/life safety plan CAD drawing to mandatory 1/4" scale (if
possible) showing seating and table/bar arrangements witli
appropriate travel paths and width measurements for the following:
• Between seating.
• isle width clearances.
• Business name and address must be documented on the plan.
• Ail assembly occupancies require gross and net measurements to
include measurements and square footage of each room.
• All areas must be labeled indicating their use on the floor plan.
• Designer/Architect to include all occupant load calculations on the
plans.
• Door measurements, stairs, and corridor widths shall be included on
the plan.
• Door measurements, stairs, and corridor widths shall be included on
the plan.
• Plans are to show all occupant load calculations for the different
areas.
• Indicate on the plan any life safety equipment, i.e. fire sprinklers, fire
alarm, etc.
• Panic hardware must be indicated on exit doors with loads of 1J0 or
more occupants.
• Fire occupant loads must be included for all interior spaces and
enclosed exterior spaces.
• All assembly occupancies shall provide proof of crowd manager
training per NFPA 101:12.7.6.
Apply for Certificate
Occupant Load Applicatioi
7/20/21
Submitted into the public
record for item(s) 191.4
on 7f22, 2f , City Clerk
7/20/21
Upload Documents
You will receive an email from ePlan/ ProjectDox to proceed with
uploading drawings into ProjectDox. You will need to create an account.
If you need help, we have directions for submitting documents and
drawings. About ePlan.
How to Submit Plans (Drawings) & Documents Electronically
Access ePlan/Proiec
Await Inspection
After your documents have been reviewed, we will reach out to schedule
an inspection.
Download Certificate
After the inspection is complete (assuming you passed), your certificate
will be added to your ProjectDox folder and available for download.