HomeMy WebLinkAboutExhibit7THRESHOLD INSPECTION PLAN
PROJECT TITLE: CITY OF MIAMI - COLLEGE OF POLICING
A/E PROJECT NO. 60011889
A/E OF RECORD: SPILLIS CANDELA DMJM
PREFACE: These guidelines are intended as "guidelines" for the
Special Inspector and are not intended to surrogate the
requirements of the Building Official. Further, it is not
intended that the Contractor's contractual and statutory
obligations are in anyway relieved or foregone by the presence of
the Special Inspector. The Contractor has the sole
responsibility for deviations from the Official Contract
Documents. The Special Inspector does not replace the duties of
the Building Official nor the quality control personnel of the
Contractor.
I. OBLIGATIONS
The Special Inspector is obligated to both the Owner and the
Building Official for observing that the work is executed in
substantive accordance with the Official Contract Documents,
which are defined in the Project Manual.
It is the obligation of the Special Inspector to notify the
Contractor, the Building Official, the Architect -Engineer of
Record, and the Owner of the following:
A. The use of materials, equipment, or workmanship which do not
conform to the Official Contract Documents or which will cause
improper construction which is not acceptable.
B. Work which is not being done in accordance with the approved
Official Contract Documents.
C. The recommended removal or repair of faulty construction or of
construction performed without inspection and not capable of
being inspected or tested in place.
D. File reports hereinafter described with the Building Official,
and the Architect -Engineer of Record and the Owner.
E. Write and file such other structural reports as may be
required by the Building Official.
F. Make other structural inspections as required by the Building
Official.
II. REPORTING INFORMATION AND OBSERVATIONS
The Special Inspector's reports are secondary to actual
observation during construction. However, they are of
extreme importance in that they enable the Building Official,
the Architect -Engineer of Record, and Owner to keep current
with the work while it is in progress and will be of value in
case of changes in the structure or its use in the future.
The report may consist of a record of the progress, working
conditions, observations given to the contractors, deviations
from the Official Contract Documents, and problems
encountered. The reports shall be in writing and shall be
made out promptly at the end of the period covered. The
reports may consist of and or all of the following:
A. Report of each inspection.
B. Jobsite log of area inspected.
C. Special records, mill tests, concrete tests, welding tests and
reports, soil compaction tests, soil densification test and
reports, and welding reports.
D. Record of placing and curing concrete.
E. Changes made in the field during a particular observation.
F. Photographs.
G. Erection of structural steel.
Reports shall be filed weekly.
III. PREPARATION CHECKLIST
A. Note permits which have been obtained
B. Licensed contractor's representative and contact person
C. Adequate supervision/organization/men/equipment
D. Approved Official Construction Documents/shop drawings/
shoring and reshoring plan/activity schedule
E. Log/daily diary set up
F. Arrangements for testing have been made
G. Preconstruction meeting/construction coordination meetings
IV. DETAILED INSPECTION CHECKLIST
The Special Inspector shall inspect the following:
/ A. Foundation
1. Excavation/subsurface preparation/bearing capacity
2. Independent testing records/approvals (density
tests, and soil densification records/approvals
3. Placement and sizes of anchor bolts/rebar/dowels -
grade of steel
4. Concrete cover
5. Provision for utilities/conduit in structural
elements (note structural integrity of footing)
6. Moisture protection
7. Excavation, effect of construction on existing
structures
8. Grade and elevations verified by Contractor
9. Review of soil reports/borings/density test reports
10. A testing laboratory will provide the inspection,
tests and reports of the soil densification. A
testing laboratory will make the required soil
density (compaction) tests. Include those reports
with those required herein.
J B. Concr
Proper inspection requires adequate inspection personnel
during the placing of concrete and finishing. It includes
preparations prior to the start of placement such as proper
formwork, placing reinforcing, cleaning the surface of the
formwork, etc., as well as proper protection and curing of the
finished concrete.
/ 1. Rebar
a. check shipment mill inspection/damage/excessive rust
b. size/grade/bending
c. placement (location - disturbance after placement)
d. support/tie/degree of support and stability during pour
e. cover
f. length and splices/laps/hooked bars
g. check from engineering drawings
h. clean before pour
i. record and deviations from drawings such as additional
steel or larger diameter bars
✓2. Provide signed and sealed letter from "shoring" specialty
engineer indicating adecuacy of shoring and reshoring.
/3. Placement
a. methods used for transportation, handling and
placing concrete shall be reviewed for avoidance of
whatever may cause poor consistency control or
segregation.
b. the number and condition of concrete vibrators shall
be verified including extra stand-bys to eliminate
air and rock pockets.
c. preplanned construction joints or emergency joints
should be substantiated. Joints shall be located
and made so at least to impair the strength of the
structure. Joints shall be prepared prior to making
the secondary pour.
d. drop, vibration, consolidation (metal deck will not
withstand heavy concrete loads - CAUTION)
_e. tests conducted
f. water added
g. age
h. disruption to rebar
i. clean up prior to placement
j. slump test on deck (not at truck) prior to placement
4. Curing and Strength
a. special provisions called for
b. test reports verified
c. additional tests needed
d. reshoring
e. removal of forms
f. finishing, repairing surface defects
5. Existing Concrete to be repaired
a. Verify actual limits of unsound concrete have been
removed
b. Verify concrete has been removed behind existing
reinforcing steel when required by the design
drawings.
c. Verify acceptable section Toss of reinforcing steel.
d. Verify existing reinforcing steel properly cleaned.
e. Verify existing concrete surface adequately
prepared.
f. Verify the specified materials and procedures are
utilized in repairing the existing concrete.
g. Verify repair materials are properly cured.
IC. Steel/Structural
a. Erection procedures (sequence)
b. Accepted shop drawings
c. Mill test reports, if required by specifications
1. The structural steel may be inspected in the shop by a
testing laboratory, primarily for welding, shop bolting
and quality of materials. See AWS Chapter 6 and
specifications.
2. The structural steel will be inspected in the field by a
testing laboratory for field welds and field bolting
(torquing).
3. Bolting: Verify that bolts have proper torquing, if
specified.
4. Surface finish/shop construction - galvanized, painted or
bare/any apparent manufacturing defect.
5. Identification of ASTM specification mark
6. Welding electrodes
7. Field verification for loading during construction for
composite beam.
8. Field verification of steel sections and their location
and compliance with shop drawings.
9. Inspection of welds and stud welding by testing lab before
being covered.
10. Fire protection: Spray fireproofing will be inspected by
a testing laboratory.
D. Metal Floor and Roof Deck
1. Verify proper gage and profile.
2. Verify installation complies with shop drawings
(single, double and triple span conditions).
3. Verify welding of deck complies with specified
fastener pattern and weld size. Verify welded
sidelap fasteners are utilized where specified.
4. Verify deck galvanized finish complies with project
specifications.
E. Frame
1. Connections
a. Connection as indicated on design drawings or shop
drawings is installed correctly.
b. alignment/plumbed
F. Roof
1. Connection details
2. Drainage/slope - roof drains
3. Parapet walls/bracing
4. Equipment supports
5. Signs and appurtenances
6. Overflow scuppers and outlets
7. Ponding immediately after rain
G. Glazing/Precast Concrete Panels
1. Verify that connections comply with shop drawings.
2. Accepted system/compliance with accepted shop drawings
3. Safety glazing identification
4. Alignment deflection
5. Testing laboratory will inspect the welding for concrete
panel connections.
H. Masonry
1. Non -reinforced
a. tie beam/tie columns - spacing size/location/
placement of concrete before or after black wall/
dovetails if required/vertical inserts
b. durowall/reinforcing
c. grouted cells
d. mortar mix adequate
e. shear transfer - clips/dowels - as called for
2. Reinforced and Partially Reinforced
a. steel placement/lap lengths/location of poured in place
dowels/vertical steel in same cell as dowel/clean out
opening at bottom of cell to be grouted.
b. alignment of cells to be filled/slump of grout/cells to
be wet before pouring/only grout the cells as
specified/cells adjacent to opening and corner to be
grouted/vertical bar embedment length in tie beam
c. verification of filled cells/observation holes
d. mortar mix adequate
I. Miscellaneous Structural Components such as Handrails,
Guardrails, Stairways and Light Gauge Metal Framing
1. Verify light gauge metal framing and connections with shop
drawings.
2. Verify handrails, guardrails, stairways with shop
drawings.
J. General Observations
1. Check Local Failures
a. hairline cracks
b. deflection
c. settlement
d. overloads due to storage of materials
e. honey combing/exposed reinforcing steel/rust spots
f. structural member behavior in case of 60 mph wind
g. design and presence of barricades as required.
K. Records
1. Concrete
a. Slump test ASTM C143
b. compression tests of molded cylinders ASTM C31, C39
three specimens per 50 cy
c. cylindrical cores (ASTM C42)
2. Soils
a. Densification and inspection reports
b. Soil compaction and reports
3. Steel: Welding inspection reports, check welder's
certification
4. Building Official Standard Reporting Forms, as may be
required
5. Other records as may be deemed necessary by the Special
Inspector such as:
a. concrete test cylinder reports
b. changes by the design A/Efied
c. soil density test reports
d. observe any holes drilled in slabs, walls, columns
without prior acceptance
e. any exposed reinforcing steel exposed at face of
reinforced concrete member
f. at end of the week special inspector shall issue a
report regarding status of discrepancies found in that
week or before if not fixed
g. send copy of inspection reports to Architect, design
Engineer, Owner,Contractor, and any other as requested
by the Owner.