HomeMy WebLinkAboutSystem Detailtianary power"'
System Detail
System Proposed Configuration
-48V, 1200A rectifier plant:
1. Basic System:
Part Number: MP00000386
Two rectifier shelves with 4 rectifier slots each
• Single Phase Individual AC input per shelf
• provides up to 1200A @ 48V DC
- 7'-0"Foot High, 23 Inch Wide Seismic Rack
- One 1200A -48V Battery Termination Panel with No LVBD
One (8) Position GJ Circuit Breaker (225A-600A)
One (1) 600A Three Position High Capacity Circuit Breaker
Full Featured Modular Controller — XC2000
TCP/IP interface and SNMP
2. Rectifier:
Part Number: X7500A1
- Input Voltage: 180-264VAC
- Output Current: 150 amps @ -48Vdc
- Temperature: 65°C
A. Irshad
-48V Modular Plant
Profile Drawing
-48V, 1200A
MP00000386
Bay 1
23', 7', Seismic
i
i Minimum 3u Specie
H
-48V, 1200A Denary
TermYnellon Panel, with no
LV BP.
6-750MCM per polarity
10101)
411V OC Pielrlputlan Panel.
(e) GS breaker poiitlona
• (r433)
i
-46V Recllfler Shelf M1
(SX231M-A1)
.RV Recliner Shelf M2
(SY-231M•A1)
City of Miami
Telecom Power
Technical Proposal
4 of 10