Dranetz-BMI 3100 PQPager — Power Quality Analyzer
M Pap)
Specifications for the 3100 PQPager
Specifications
Voltage Inputs Phase A, B, C, Neutral
Power Types Single phase, split single phase, 3-phase 4-wire wye, 3-phase 3-wire delta
Supported
Measurement 0-150 Vrms, t250Vpk or 0-600 Vrms, t1000Vpk (user selected) 50/60 Hz
Range
Accuracy ±1.0% of reading ±0.5 digit
Sampling Continuous; 32 samples/cycle 50160 Hz
Events Recorded Sags, swells, interruption, restored, transient, contact closure(two), rain/average/max RMS strip chart Event
signatures Pre- and post -samples recorded: 128 RMS samples for RMS sags, swells 4 cytes of waveform data
for transients
Contact Closure Two inputs for dry contacts; NO or NC (user selected)
Input
Event Memory Sufficient for at least 32 events, including event signatures, plus at least 30 days of strip chart
Operating NEMA 4X, -40iF to 1221F -401C to +501C
Environment
Instrument Power 110V-240V or 220V-480V, user selected 50/60Hz internal automatically charged 15-minute batteries Memory
contents preserved for 10 years
Certifications UL, FCC, CE, and ISO-9001
City of Miami
Telecom Power
Technical Proposal
6 of 10
/daticirTrIVII?"mw'
• PES
PES is a powerful yet easy -to -use software package that is ideal for systems comprised of one to fifty instruments. PES can be
configured for dial -up communication, automatic download, call back, or direct connection. The features available in PES depend on
the instrument to which it is connected.
Modes of Operation
Threshold Customize threshold settings for RMS
Settings disturbances, interruptions, and transients,
Pagers & Configure a PQPager to make up to four separate
Telephone phone calls to a variety of paging services and/or
Numbers IBM/PC master stations.
City of Miami
Telecom Power
Technical Proposal
7 of 10
ttporire"
Outgoing
Phone Calls
• Control the types of events that will be
recorded
• Specify which phone numbers will be
called when an event takes place
• Limit the number of calls in one day to
each phone number
• Control whether oldest or newest events
will be saved if memory is completely
filled
Scheduling Specify which remote instruments will be
Downloads contacted by your master station PC, and how
frequently.
-„_''sSII I �11 u'r Pil�Ni'.7 imrri-,llil,lll!
Real Time When your PC is connected to an instrument via
Meters RS-232 serial connection or modern, you can
select Meters Mode to see live RMS voltage,
current, and power parameters.
(POPager RMS volts is shown.)
City of Miami
Telecom Power
Technical Proposal
8ofio
#�ti ary lxrvkr4'
Real Time When your PC is connected to an instrument via
Scopes RS-232 serial connection or modem, the PES
Scope Mode lets you view from one to four
separate displays of live waveforms, phasors,
polar plots and/or FFT spectra.
(PQPager voltage signals are shown in this
example.)
The 3100 PQNode is the ideal power quality tool for utility key account programs. It has the unique,
patented ability to communicate directly to account executives, managers, and customers through its
built-in voice -mail -like interface. It can also send messages directly to up to 4 pagers thereby bypassing
the traditional bottleneck of a utility master station.
In addition to monitoring 3-phase voltage for Dranetz-BMl-grade disturbance information, the 3100
PQNode also keeps track of two contact closure inputs that can be connected to thermostats, flood
switches, customer equipment, or security alarm systems.
Like all PQNodes, the PQPager uses PES software, allowing power quality engineers to automatically
retrieve waveform signatures of every event for quick, accurate diagnosis. The PQPager conforms to
IEEE and IEC standards for classifying and recording disturbances and is UL, FCC, CE, and ISO-9001
certified.
Bill of Material:
One (1) 3100 PQPager
One (1) PES Computer Software
One (1) Lot of interconnecting hardware
One (1) Rack -mount, pull-out, Industrial PC (Windows XP Pro)
City of Miami
Telecom Power
Technical Proposal
9 of 10