Loading...
HomeMy WebLinkAboutSpecificationst'startia�pov;re,� Dranetz-BMI 3100 PQPager — Power Quality Analyzer M Pap) Specifications for the 3100 PQPager Specifications Voltage Inputs Phase A, B, C, Neutral Power Types Single phase, split single phase, 3-phase 4-wire wye, 3-phase 3-wire delta Supported Measurement 0-150 Vrms, t250Vpk or 0-600 Vrms, t1000Vpk (user selected) 50/60 Hz Range Accuracy ±1.0% of reading ±0.5 digit Sampling Continuous; 32 samples/cycle 50160 Hz Events Recorded Sags, swells, interruption, restored, transient, contact closure(two), rain/average/max RMS strip chart Event signatures Pre- and post -samples recorded: 128 RMS samples for RMS sags, swells 4 cytes of waveform data for transients Contact Closure Two inputs for dry contacts; NO or NC (user selected) Input Event Memory Sufficient for at least 32 events, including event signatures, plus at least 30 days of strip chart Operating NEMA 4X, -40iF to 1221F -401C to +501C Environment Instrument Power 110V-240V or 220V-480V, user selected 50/60Hz internal automatically charged 15-minute batteries Memory contents preserved for 10 years Certifications UL, FCC, CE, and ISO-9001 City of Miami Telecom Power Technical Proposal 6 of 10 /daticirTrIVII?"mw' • PES PES is a powerful yet easy -to -use software package that is ideal for systems comprised of one to fifty instruments. PES can be configured for dial -up communication, automatic download, call back, or direct connection. The features available in PES depend on the instrument to which it is connected. Modes of Operation Threshold Customize threshold settings for RMS Settings disturbances, interruptions, and transients, Pagers & Configure a PQPager to make up to four separate Telephone phone calls to a variety of paging services and/or Numbers IBM/PC master stations. City of Miami Telecom Power Technical Proposal 7 of 10 ttporire" Outgoing Phone Calls • Control the types of events that will be recorded • Specify which phone numbers will be called when an event takes place • Limit the number of calls in one day to each phone number • Control whether oldest or newest events will be saved if memory is completely filled Scheduling Specify which remote instruments will be Downloads contacted by your master station PC, and how frequently. -„_''sSII I �11 u'r Pil�Ni'.7 imrri-,llil,lll! Real Time When your PC is connected to an instrument via Meters RS-232 serial connection or modern, you can select Meters Mode to see live RMS voltage, current, and power parameters. (POPager RMS volts is shown.) City of Miami Telecom Power Technical Proposal 8ofio #�ti ary lxrvkr4' Real Time When your PC is connected to an instrument via Scopes RS-232 serial connection or modem, the PES Scope Mode lets you view from one to four separate displays of live waveforms, phasors, polar plots and/or FFT spectra. (PQPager voltage signals are shown in this example.) The 3100 PQNode is the ideal power quality tool for utility key account programs. It has the unique, patented ability to communicate directly to account executives, managers, and customers through its built-in voice -mail -like interface. It can also send messages directly to up to 4 pagers thereby bypassing the traditional bottleneck of a utility master station. In addition to monitoring 3-phase voltage for Dranetz-BMl-grade disturbance information, the 3100 PQNode also keeps track of two contact closure inputs that can be connected to thermostats, flood switches, customer equipment, or security alarm systems. Like all PQNodes, the PQPager uses PES software, allowing power quality engineers to automatically retrieve waveform signatures of every event for quick, accurate diagnosis. The PQPager conforms to IEEE and IEC standards for classifying and recording disturbances and is UL, FCC, CE, and ISO-9001 certified. Bill of Material: One (1) 3100 PQPager One (1) PES Computer Software One (1) Lot of interconnecting hardware One (1) Rack -mount, pull-out, Industrial PC (Windows XP Pro) City of Miami Telecom Power Technical Proposal 9 of 10