HomeMy WebLinkAboutMiami-Dade Water & Sewer CommentsEMORANDUM
•
•
•
TO: Robert Lav
Land
Plat
FROM: Phi ur. orres, P.E., Manager
ns Review Section
trig
elopm
Chie
ivy of Miami
..oning Department
DATE:
August 23, 2004
SUBJECT: Large Scale Development
'k Miarni-Dade Water and Sewer Department continents and reconnrnendations are as fellows:
C a iro Tower
VW SW 12 Ave bet. SW 3rd St. and SW 4 St.
V1' ter
Connect to an existing twelve (12)-in. w.m. in SW 12 Ave. N/O SW 3 St. and extend same
southerly in SW 12 Ave. to SW 4 St. and to be inter -connected to an existing eight (8)-in.
w..rn. in SW 12 Ave. and 4 St. Extend also a twelve (12)-in. w.m. westerly either in S W 3 St.
or 4 St. from the proposed 12-in. w.m. in SW 12 Ave.. to the NW or SW corner of the
property respectively, based on the need for fire hydrants and/or additional connections.
Interconnect any of the aforementioned extensions to the existing 8 or 2-in. w.m. (s) in SW 3
St. or SW 4 St at the NW or SW corner of the property respectively. Any public w.m.
extension within the property shall be twelve (12)-in. min. in diameter with two (2) points of
connection and the system shall be looped, in order to avoid dead end mains.
Los):
The gravity sewer point of connection infornratiott for this development and the size of the
required gravity sewer mains in public right ofwayare subject to an engineering analysis to be
conducted by the M-DWASD at the time a request for connection is sent io the Department,
due v.1 existing available capacity concerns in the area of the City of Miami.
GENERA!, NOTES:
The size of the required water mains will depend upon the subject property's approved zoning, being
twelve (12)-in. thin. in diameter required for high density residential, commercial, business,
industrial, hospitals, public building, etc. and eight (8)-in. min. in diameter required for low and
medium density residential zonings.
Please note that improvements to the sewage pump station (s) receiving the flow from the project
ma,, be required based on the project's sewage flow to be discharged into M DWASD's system at
the time a request is sent to the M-DWASD.
Please be advised that the right to connect the referenced property to the Department's sewer system
is subject to the terms, covenants and conditions set forth in the Settlement Agreement between the
Florida Department of Environmental Protection ("DEP") and the County dated July 27 t
993, the
First Amendment to Settlement Agreement between DEP and County dated .December 21t5t, 1995, the
First Partial Consent Decree and the Second and Final Partial Consent Decree entered in the United
States of America Environmental Protection Agency vs. Metropolitan Dade County (Case Number
93-1109 GIV-MORENO), as currently in effect or as modified in the future, and all other current,
subsea uent or future agreements, court orders, judgments, consent orders, consent decrees and the like
entered into between the County and the United States, State of Florida and/or any other
governmental entity, and all other current, subsequent or future enforcement and regulatory actions
and proceedings.
if you have any questions, please do not hesitate to call me at 305-669-74558.