6/16/2004
Central
3rd Floor Training Room Belts
Cracked, 2nd Floor Roll Call
Belts
$ 664.58
41967
10113835
5/25/2004
Central
Bldg A/C Down
Chillers
$ 2,057.77
41967
10113833
5/21/2004
Central
Backup Chiller
Replace flow switch
$ 944.24
41724
10112164
11/19/2003
Central
Trane/T72F/1-3603279
Freezer & Evaporator Fans not
operable
$ 170.00
41724
1011245
11/15/2003
Central
Trane/T72F/1-3603279
Can-ier/JCA273D
Evaporator fan not running,
Elevator room evaporator
blower loose.
$ 487.50
41724
10112156
11/17/2003
Central
Carrier/JCA273D/11 C1 B48669
Training Room and 4th Floor
Adjust ceiling thermostats
open 4 supply dampers
adjust belt in roll call
$ 877.50
41724
10112059
11/7/2003
Central
Unk
Install new controller in Chiefs
office, remove damper in supply
duct
$ 430.72
41724
10112363
12/8/2003
Central
Carler/39BA060B12/75367636
UPS Room Replace fan motor
$ 596.75
231209
10110365
6/4/2003
Central
Floor 2,4,5 was off due to
Fire Alarm system
$ 190.00
235285
41724
10112050
11/5/2003
Central
Room 409
Install new Johnson Control
Thermostat
$ 329.52
235285
10112016
10/31/2003
Central
UPS Room
Replace two belts in both
UPS Rooms
$ 260.00
235285
10112027
11/4/2003
Central
Liebert1FH245AUR10
Computer Room
Remove blowers and replace
bearings
$ 820.72
235285
10111641
9/24/2003
Central
Carrier/JCA273D
Can-ier/1101848669/CompRm
Low on Refrigerant/repaired
UPS Room adjust motor pulley
and alignment
$ 672.00 ;
41967
10113725
5/14/2004
Central
Roof
York Chiller
VCAL0044SC46XA
Leak on chiller water supply line
$ 397.75
41967
10113725
5/14/2004
Central
Chiller
Replace chilled water pump
$ 1,361.35
41967
10113697
5/12/2004
Central
Chiller
Chillers down, broken pipe,
pump leaking, repair
condenser water loop
$ 2,146.33
41967
10113356
3/26/2004
Central
Trane RTHB180FLE
Ser/U96G05710
Trane RTHB180FLE
Ser/U96G05711
Install two new module boards
and set controls
$ 2,080.00 i
41967
10113483
4/20/2004
Central
Trane RTNB180FLE
Ser/U96G05710
Added refrigerant
$ 467.50
41967
10113357
3/26/2004
Central
Elevator Room in Parking
Garage
Install wall a/c unit
$ 445.00
41967
10113334
3/25/2004
Central
Trane RTHB180FLE
U96G05711
Chiller #2 need new key board
$ 357.50
41967
10113327
3/24/2004
Central
Install new sensor in Unit #1
New thermostat in 4th Floor
$ 542.13
41967
10113225
3/18/2004
Central
Chillers
Check Freon on both chillers
Adjusted belts on 5th floor
and Roll Call Room, blew out
pneumatic air line of water
$ 455.00
W �
3/10/2004
2,
41967
a• 7
10113155
�;� e
i:�
Central
Pneumatic Lines
Replace air dryer and install
new pneumatic air lines
$ 2,850.00
41967
10113148
3/9/2004
Central
Pneumatic Lines
Check system found water in
the pneumatic lines which
blew out controllers
$ 275.00
41967
10113099
3/2/2004
Central
York YCALG0445SC46XA
Repipe make up water line
$ 1,295.00
41967
10112918
2/12/2004
Central
Chiefs office
4th Floor Drain Line
Replace pneumatic regulator
in Chiefs office, and checked
our drain line might have
a problem with water pressure
relief valve
$ 478.47
41967
10/112915
2/11/2004
Central
Fire Dept Dispatch not
cooling;water leak 4th floor
Replace damper - Fire Dept
$ 535.00
41967
10112862
2/3/2004
Central
Chillers
Air compressors not working
$ 552.50
41967
10112851
1/30/2004
Central
A/C in Computer Room
Low on Freon, found leak at
liquid line, repair
$ 463.00
41967
10112766
1/22/2004
Central
Liebert/CDF291A
Replace fan blade
$ 571.94
41967
10112565
12/24/2003
Central
5th Floor and lst Floor
Check Pneumatic controller on
5th Floor, replace Johnson
control. Checked pneumatic
control on 1st floor.
$ 1,071.48
41967
10112415
12/12/2003
Central
Adjusted controllers on 2nd, 3rd
& 4th Floor, the 5th Floor
required a new controller
$ 422.50
41967
10112362
12/6/2004
Central
UPS Room
Carrier 39BA060B12
Ser/75367636
Breaker tripped in unit found
fan motor totally bumed, needs
replacement
$ 390.00
41967
235285
235285
41967
41724
41724
41724
41967
10112436 12/17/2003 David Hering Rheem #3IRAWD100CAZ
Training Center
10111616
10111506
10114018
10112144
10112279
10112603
9/17/2003
9/14/2003
6/11/2004
11/14/2003
11/25/2003
1/6/2004
North Station
North Station
North Station
North Station
North Station
North Station
Trane/RAUCC25ECW
2nd Floor Air Handler
2nd Floor Not Cooling
Air Handler
Trane/RAUCCO25ELW
Ser/CO2F05378
Trane/RAUCC25ELW
Ser/CO2F05378
Remove expansion valve and
install new expansion valve,
add freon.
Repair wires in A/C Unit
Air handler found to have high
voltage going through board.
Unit not running due to a smoke
detector that interacts with
controls.
Blown fuse on air handler,
panel loose, retightened and
replace fuse.
Replace timer.
Replace motor
TOTAL
$
$
268.72
227.50
292.50
292.50
299.39
861.25
390.00
$ 28,290.61