HomeMy WebLinkAboutIII.3. Site Utility Study■
July, 2007
17th ST. BISCAYNE BLVD,
MAJOR USE SPECIAL PERMIT
SITE UTILITY STUDY
PREPARED FOR
Midgard Management Inc.
Kimley-Horn
® and Associates, Inc.
July, 2007
17" ST. BISCAYNE BLVD.
MAJOR USE SPECIAL PERMIT
SITE UTILITY STUDY
PREPARED FOR
Midgard Management Inc.
Site Utility Study
Introduction
17`h ST. and Biscayne Blvd is a proposed (2) two tower (tower (1) of 55 stories and tower (2)
of 49 stories) mixed use development to be located west of Biscayne Boulevard, between
NE 171" Street and NE 17th Terrace and east of NE 2nd Avenue in the City of Miami, Miami
Dade County, Florida (see site location map). The proposed development will be situated on
a 2.37 + acre site and shall consist of 613 residential units and 289 hotel units. There shall be
a total of 1,418 parking spaces to adequately serve all areas within the proposed
development.
Table 1
Project Summary
17" ST. AND BISCAYNE BLVD.
Site Utility Study Page 2
F1o6r Area
Occancy
Rp
Units .
(SF)
Parking (Gross)
1,418
Residential Units
613
Hotel Units
289
Retail
_________
149,086
17" ST. AND BISCAYNE BLVD.
Site Utility Study Page 2
J (IVt LLIVU I
Z
N (�
NE:22ND ST zNE ST NE 22ND ST
NE 21 ST ST
NE 20TH TE
JE 20TH ST
NE 19TH TE
NEI 21ST ST o
0
NE 20TH ST Cf)
NE 19TH ST NE 19TH ST
0 m
o =
N W 18TH ST
z
JE 17TH TE U
Q 17TH TE Un �Ty T
� J
U n
NE 17TH ST
Q' CT
L ATION
z z NE 16TH ST z
NE 16TH ST =
cn
Q U �
Q
U� NE 1 TE m NE 15TH ST
15 H ST
w w 14TH TE
z z
f -
U
NE 14 H ST NE 14TH ST
C)
NE 13 H TE 13TH TE <
E13HST 395 co
w NE 13TH ST
Iftey-Horn and Associates, Inc.
1691 Michigan Avenue
Suite 400
Miami Beach, Florida 33139
Phone: 305-673-2025
Fax: 305-673-4882
17th ST. AND BISCAYNE BLVD
SITE LOCATION MAP
Drainage
Existing Drainage System
Based on site observations and available information, there is an existing drainage system serving
the property. The existing system will be demolished and a new storm water management system
will be constructed to retain the runoff generated by the proposed improvements, as required by
code (see below).
Proposed Drainage System
The drainage system for the proposed development will consist of drainage wells and exfiltration
trench for water quality purposes, and to facilitate on-site disposal of storm water runoff. The 5 -
year design storm event will be used to design the storm water management system, in accordance
with Section D-4, "Water Control", of Part 2 of the Miami -Dade County Public Works Manual.
Based on preliminary calculations, it is anticipated that six (6) drainage wells will provide sufficient
capacity to dispose of the 5 -year 24-hour design storm water runoff generated by the proposed
development. Preliminary drainage computations for the project areas are provided in Attachment `B"
The final drainage design for the proj cot shall be in conformance with the requirements of the Miami -
Dade County Department of Environmental Resources Management (DERM) - Water Control
Section, Florida Department of Environmental Protection (FDEP), and other local, state and federal
regulatory agencies having jurisdiction over the project.
Flood Criteria:
The proposed project site grade elevations will be designed to meet floodplain management
criteria according to Federal, State, Miami -Dade County and City of Miami standards as follows:
1. The subject property is located in PANEL 183 of 625 of COMMUNITY -PANEL NUMBER
12025C0183 J of the Flood Insurance Rate Map (FIRM). According to the National Flood
Insurance Program, the property is located within the following Flood Zones:
(1) Flood Zone AE and has a base flood elevation 9.0 (See Attachment A.)
(2) Flood Zone X (See Attachment A.)
17" ST. AND BISCAYNE BLVD.
Site Utility Study Page 4
2. Miami -Dade County Flood Criteria elevation is estimated to be 5.0 ft. NGVD. This will be
used to determine proposed minimum site grade elevations.
3. The average October ground water table elevation is estimated to be 2.0 ft. NGVD. This will
be used as the control water elevation for storm water management calculations (Source:
Miami -Dade County Public Works Manual, Volume II - Design Standard Detail WC 2-2).
II. Water Distribution System
The water mains owned and operated by the Miami -Dade Water and Sewer Department (IVIDWASD)
in the vicinity of the project are shown in the Table 2 below.
Table 2
Existing Water Mains
Location
Between
Water Main(s)
Biscayne Blvd
NE 17th Street and NE 17t1' Terrace
16"
NE 2"d Avenue
NE 17"' Street and NE 17t1' Terrace
6" and 20"
NE 17`h Street
Biscayne Blvd and NE 2"d Avenue
6" and 12" (Half of 17th
Street).
NE 17th Terrace
Biscayne Blvd and NE 2nd Avenue
2"
In accordance with Miami -Dade Water and Sewer Department (MDWASD) criteria, a 12 -inch water
main is required along the frontage of all commercial developments. In addition, the City of Miami
Fire Department may request additional fire hydrants be placed in the vicinity of the subject project.
However, a final determination of the points of connection and requirements will not be provided by
17th ST. AND BISCAYNE BLVD.
Site Utility Study Page 5
MDWASD until Water and Sewer Agreement is requested by the owner. Water service meters would
need to be purchased by the owner and installed by MDWASD officials. See Attachment "C" for a
copy of the MDWASD water atlas sheet for the project area.
III. Sanitary Sewer Collection System
Table 3 depicts the sanitary sewer mains owned and operated by the Miami -Dade Water and Sewer
Department within the vicinity of the project.
Table 3
Existing Sanitary Sewer Mains
Location
Between
Sanitary sewer
line(s)
Biscayne Blvd
NE 17th Street and NE 17th Terrace
10" and 8" (Gravity)
NE 2"d Avenue
NE 17th Street and NE 17t1' Terrace
16" FM Sludge Line and
8" (Gravity)
NE 17th Street
Biscayne Blvd and NE 2" d Avenue
8" (Gravity)
NE 17th Terrace
Biscayne Blvd and NE 2" d Avenue
8" (Gravity)
The existing gravity sanitary sewer main along the frontage of the property may have sufficient
capacity to accommodate the proposed development. A letter of availability and further coordination
with MDWASD is recommended to verify the proposed sanitary sewer service connection points and
requirements for this project. MDWASD and DERM may require upgrades to the existing sanitary
sewer system, but this can not be determined without a request for a Water and Sewer Agreement.
MDWASD Pump Station #30-0002 at 925 Biscayne Blvd receives the flows from these
mains. As of 7/02/07, this pump station is operating at an average yearly NAPOT of 3.78
hours which is 37.8% of its design capacity. The pump station projected NAPOT is 5.98
hours, which is 59.8% of its design capacity. Therefore, anew sanitary sewer pump station or
_ 17th ST. AND BISCAYNE BLVD.
Site Utility Study Page 6
upgrades to said pump station may not be required for the proposed development. A final
determination regarding the status of the existing transmission system and the need for
possible improvements will not be made until construction plans are submitted to the Miami -
Dade County DERM Wastewater Section and a Sanitary Sewage System Capacity
Certification Letter is issued. Please refer to Attachment "D" for Pump Station Monthly
Information.
Table 4
Water & Sewer Flow Generation
Type of
Total Average Dally Flow
Qccn anc
Quante
-ITsa e rate,
Apartment
residence
613 units
200 GPD/unit
122,600 GPD
Hotel Units
289 units
100 GPD/SF
28,900 GPD
Retail
149,086
5/100 GPD/SF
7,455 GPD
Total Anticipated
Flow
158,955 GPD
17" ST. AND BISCAYNE BLVD.
Site Utility Study Page 7
IV. Solid Waste Generation
Solid waste generated by this project will be collected in standard on-site containers for
refuse and recyclables. Regular pick-up service will be provided either by private hauling
companies and/or by the City of Miami Solid Waste Department, who will transport the
waste to Miami -Dade County's or private disposal and recycling facilities. The volumes of
solid waste projected to be generated by the project are shown in Table 5.
Table 5
Solid Waste Generation
:.Type of
";
Total Solid Waste
'lJccu .aic
uantit
Q"
sa , ,
: _ U'e rate , .
Generat ed ons/Da .
Apartment
residence
613 units
5 lbs/unit/day
1.53
Hotel units
289 units
4 lbs/unit/day
0.58
Retail
149,086 SF
7.47 lbs/100 SF/day
5.57
Total Anticipated Solid Waste Generated
7.68
17`' ST. AND BISCAYNE BLVD.
Site Utility Study Page 8
Attachment A
Maps
Page 9
Z
O
S
Kimley-Horn and Associates, Inc.
1691 Michigan Avenue, Suite 400
Miami Beach, Florida 33139
Phone: 305-673-2025
Fax: 305-673-4882
17th ST. AND BISCAYNE BLVD
F.I.R.M. FLOOD INSURANCE
RATE MAP
—4, 4�« 1,
!
I�
Ne Mitt ST�
l
APPROXIMATE SCALE
City U f
-
T+ 500
scc rr-
535 '
13TH Si
c` Ml
ZONE
120650 x
4
_
F ,
Z114y --
A P
NATIONAL A
4?JU1Nk R R
Jr
Nr 1714 FE
3
,�...
k
I'
TION SIM
I I FLOOD INSURANCE RATE •;IAP
i
fL
_
z !
DADE COUNT ry, 1
ZONE AE
1. 1RIDI: I
`
IN
AN Y
p 4tC ORATED AREAS
s =
1 l 101
i
-
PANEL 183 O 625
.... TE
ZONE AE
ht 1STH
_
ILL
x
COITUS:
. - ..: . -.".. E"., <_ ,
x :: - - :. .,._
''
t -,_ {ytlk•AAfY t- xn}t pdtaL 5F{11
_
tH St. ._..
_
:
E
I Y,Y: 'b iy' n7
•
•.'. ,19TH TE.:.: _
- `
36 4hr
z ..... ,:' NC 3RTH ST .a.
♦ . x. I:[ U : _:d+ -
_ _
o
ij-
F 4
... r ..... .,.,
NE 13TH lE -
13tH TE ;_ _ .
••
MAP NUMBER
,.,.
..._
NE
- -
�!
� •
t
i -- i
4'1P REVISED: ,
1 IR4 i
! I
j
s
{,A
r
•' ZONE AE;
"(EL it)
rt. r
i � Feaernn.mrryr T �?�n A�rt;r.t ,a fir
r
_
�
t,in TE
4 -
�
'IT+:s Is an ohieml cepy o? a portion o(tha ar ova retarencad Good map. it
NE tS{N TL
, Meapadae4 not ! eCt the
Waa9 extracted UAi�1T� iT tln LeinInformation
;{SH SE
�.
mis ^9Cs h
or ameadmonts wh ch may Rave boon made subsequanf Ra ihtr data ant a
titl d k F tfi 11 t product i M at n about National Flood I surance
NH .............:.
.. ..P.,
< > . _, , , _
;::�
Program Aood maim check Tho FEMA Floud MapStora at wmv.mso,foma.gov
Kimley-Horn and Associates, Inc.
1691 Michigan Avenue, Suite 400
Miami Beach, Florida 33139
Phone: 305-673-2025
Fax: 305-673-4882
17th ST. AND BISCAYNE BLVD
F.I.R.M. FLOOD INSURANCE
RATE MAP
n.�
f£'
«t e
} .....� {,�ra3,-;=r ,k'tX5Db3;ur�si,�.1.... ......� .5 _ . ,,.,.a'.::ao-zr •:.<.r«...� P �yr1'. rd,r s C ; �, �r` "�� `���'� .
� s r?
s! tR t } ' 1fnr s
54
} t Irtitff T7 F } f
L
7{ .
}
S
19 it
53
�r rr t
.ris,ridrw
w lfd�6�wze 1 �•asrrrsr rxs,� ;,� F..
m
z4 Ri
SITU
P .St
— # s
4 „JJ
6.5
11,
C
e� « ' eu &d4i4ii
s V « d tt,`ynm
CM 1691 Michigan Avenue
—®suite 400 17th ST
Miami Beach, Florida 33139 .AND BISCAYNE BLVD.
Kimley-Horn and Associates, Inc. Phone: 305-673-2025
Fix' ins—R73-48R7 FLOOD CRITERIA MAP
{O
tea'' `
}�}f}$�
rrax
r
4t
ILP
4 144
(3;
174
- 7 i
? ECT ,
I
i���F4�
"
cit:
L
X; V
4, f 540Z
G7 to tv Ea nil y
'L e-........._........ _-,c>,>..._--.....�>.�,.,,,, C 59-# v' PAL
rww
{ ..A
[ ... i eA r• !. o i [j13
a .�*
r(ab
94t4 4 126?"
". xa3 T1#
i _ t 2�MM%A i�KRi?i
NOTES:
I. CONTOUR INTERVAL 1.0 FOOT:
I ; r '" o (Except at Inde tad)
1691 Michigan Ave
❑ — ❑ Suite 400
Miami Beach, Florida 33139
Kimley-Horn and Associates, Aw Phone: 305-673-2025
Fax: 305-673-4882
17th ST. AND BISCAYNE BLVD.
AVERAGE OCTOBER GROUND
WATER LEVEL 1960-75
Attachment B
Preliminary Drainage Well Calculations
Page 10
17th ST. AND BISCAYNE BLVD.
City of Miami, Florida
'IRAINAGE CALCtTLATIONS.
DRAINAGE N'ELL�
(MASS DIAGRAM DER1lM CRITERIA)
1. Site Data:
A. Average October Water Table Elevation = -2:00 " NGVD
B. County Flood Criteria Elevation =
SD`'NGVD
C. F.I.R.M. or FEMA Base Flood Elevation =
9
Zone AE
D. Average Crown Road Elevation =
5:75
,"NNGVD
E. Average Existing Onsite Grade Elevation =
°5.75.
'NGVD
F. Proposed drainage inlet grate elevation =
5.00
NGVD
2. Total Contributing Drainage Area (A): 2.37 Acres
A. Impervious Areas:
a) Asphalt and concrete pavement = 0.43 Acres
b) Roof areas + 1/3 NE building corner = 2.95 Acres
Total Impervious Area (A1) =
B. Pervious areas:
a) Green Areas =
3. Weighted Runoff Coefficient (C):
3.38 Acres (143%)
012Acres (5%)
Runoff Coefficient Impervious (Cl) =
0:90'
Runoff Coefficient Pervious (C2) =
0.30'
C = [(A1 x Cl) + (A2 x C2)] / A; C —
1.30
C x A= Total Contributing Area; C x A=
3.08 Acres
4. Time required to generate one inch of runoff (per DERM Water Control Section D-4)
Rainfall Intensity (I) = 308.5 / [(48.6 x F-"") + t (0.5895 + F-21)]
Fre q Y F uenc 5 ;years - Frequency Curve
_ _..5
Q = CIA, V = Qt; V(I in.) = Qt(I In.)) t(1 in.) = Time to generate 1 inch of runoff
V(1 in.) = CIAt(1 in.)
l" x A = CIAt(1 in.) ;Solving for t(I in.), t(I in.) = 1" /(IC)
Time to Generate one inch of run-off t(m) = 7.09 Min.
Time to reach the inlet (tc.) 10 00 . Min.
Total Time required to generate 1 in of runoff: = 17.09 Min.
DRAINAGE CALCS_SMA.xIs
BASIN
5. Cumulative Runoff (Inflow Mass Diagram)
6. Drainage Well Design Discharge Rate:
Based on well discharge rate of 60 GPWft. Head
Headloss due
Accumulated
Lowest.hilet
Storm
to HigherSG
Time
CxA,
I
Q
"-Runoff
(Min.)
•. (Sec)
, (acres)
(inchles)
(CFS)
(CF)
8
480
3.077
6.405
19.71
9,460
10
600
3.077
6.166
18.97
11,385
15
900
3.077
5.641
17.36
15,623
17.09
1025
3.077
5.447
16.76
17,186
30
1800
3,077
4.493
13.83
24,887
40
2400
3,077
3.956
12.17
29,218
50
3000
3.077
3.534
10.88
32,625
60
3600
3.077
3.193
9.83
35,376
90
5400
3.077
2.477
7.62
41,158
120
7200
3.077
2.023
6.23
44,820
180
10800
3.077
1.480
4.56
49,199
6. Drainage Well Design Discharge Rate:
Based on well discharge rate of 60 GPWft. Head
7. Detention Time:
The drainage well structure must be designed to detain runoff for a minimum of 90 seconds prior to discharge.
Qd = Design Runoff Rate (CFS) = 16.76 CFS
Vd = Detention Volume (CF) = Qd x 90 sec. = 1508.62 CF
Vdl = Detention Volume Per Well (CF) = 251.44 CF
W = Width of Well Structure (ft.) = 8.0 ft.
L = Length of Well Structure (ft.) = 10.0 ft.
H;,,, is the minimum depth required from the top of well casing to the floor of the well box to achieve 90 second detention time:
Hmio. (ft.) = Vd] / (W x L) = 3.20 ft.
Top of Well Casing Elev. = 8.00
Elevation at Floor of Well Box (NGVD) = Top of Well Casing Elev. - Hi,,. = 4.80
Headloss due
Lowest.hilet
Oct. Water
to HigherSG
Well Structure
Well
Ri4i Elev'.
Table elev.
of Salt Water
Head: Acting
' Well Discharge
1 Well Structure Dimensions
Storage Volume
Flo.;;
(NGVD)
(NGVD)
;;;(ft.)
ori Well (fr.)
Rate (CFS) ,
-Width (ft:),
Length (ft.)
(CF)
DW -1
10.00
2.00
2.00
6.00
8.02
480
DW -2
1 10.00
2.00
2.00
6.00
8.02
80
10.0: :.
480
DW -3
10.00
2.00
2.00
6.00
8.02
80,
",
:1,0.0:
480
DW -4
8.00
2.00
2.00
4.00
5.35
320
DW -5
8.00
2.00
2.00
4.00
5.35
320
DW -6
8.00
2.00
2.00
4.00
5.35
A0.0
320
Well Discharge Rate (CFS)
40.11
Total
Storage (CF)
2400.00
7. Detention Time:
The drainage well structure must be designed to detain runoff for a minimum of 90 seconds prior to discharge.
Qd = Design Runoff Rate (CFS) = 16.76 CFS
Vd = Detention Volume (CF) = Qd x 90 sec. = 1508.62 CF
Vdl = Detention Volume Per Well (CF) = 251.44 CF
W = Width of Well Structure (ft.) = 8.0 ft.
L = Length of Well Structure (ft.) = 10.0 ft.
H;,,, is the minimum depth required from the top of well casing to the floor of the well box to achieve 90 second detention time:
Hmio. (ft.) = Vd] / (W x L) = 3.20 ft.
Top of Well Casing Elev. = 8.00
Elevation at Floor of Well Box (NGVD) = Top of Well Casing Elev. - Hi,,. = 4.80
8. Excess storm water runoff excluding well structure storage:
9. Excess storm water runoff including well structure storage:
Accumulated
Accumulated
Well
Well
well,
"Discharge
Discharge;
Accumulated
Total Overflow'
Time
Rate'
Volume
Storm Runoff
Volume
(Min.)
(Sec.)
(CFS).
(CF)
(CF)
(CF)'"
8
480
40.11
19,251
9,460
-9,791
10
600
40.11
24,064
11,385
-12,679
15
900
40.11
36,096
15,623
-20,474
17.09
1,025.28
40.11
41,121
17,186
-23,935
30
1800
40.11
72,193
24,887
-47,306
40
2400
40.11
96,257
29,218
-67,038
50
3000
40.11
120,321
32,625
-87,695
60
3600
40.11
144,385
35,376
-109,009
90
5400
40.11
216,578
41,158
-175,420
120
7200
40.11
288,770
44,820
-243,950
180
10800
40.11
433,155
49,199
-383,956
9. Excess storm water runoff including well structure storage:
Safety Factor F2.39%
Safety Factor=
Accumulated
well,
Accumulated
Storage in 1.
Discharge
TotaLOverflow
Trm0"
Storm Runoff
Well Structure
Volume
Volume
(Sec:)
8
480
9,460
2,400
19,251
-12,191.30
10
600
11,385
2,400
24,064
-15,079.46
15
900
15,623
2,400
36,096
-22,873.58
17.09
1,025.28
17,186
2,400
41,121
-26,334.61
30
1800
24,887
2,400
72,193
-49,705.70
40
2400
29,218
2,400
96,257
-69,438.30
50
3000
32,625
2,400
120,321
-90,095.37
60
3600
35,376
2,400
144,385
-111,409.49
90
5400
41,158
2,400
216,578
-177,819.95
120
7200
44,820
2,400
288,770
-246,349.56
180
10800
49,199
2,400
433,155
-386,356.02
Safety Factor F2.39%
Safety Factor=
Attachment C
Existing Utility Records
3023 ).-A
1 C4
92.
215
330
210
! I aljj,t
47
13020
27 25
2630 j (27: , le ..12e0 11
730 2731 i
)
177
17_9A
202
214
212
214 211 206
207
M
213yr, 210 -T,/
Sa
1 13744 •
21944 7 J
230
930
-AV31 _(3743'j 23a�
234 233 226/
3742
I
( V
r—ai-3 0
223
%M I �.l �R -i't — I )a d (I
iinct
F13
—41
LEGEND
GraftUna EaMentune
Bkm*s SecOoll Boundary
Caft
1-j I Privalefteruilitf
Ivert Municipal Boundary
eA
IARe-Use Une Naa, FUWICnW Une. I
IMFMC Main Emeraency Over0aw
Skidge: Une Gravity intercepter
Ougall Une
Marker Symbols
T -ent Plant Connedon We
reatTo
Reducer
Flow Meter
4146
I HE 20. -TER
4146
ILI
ME 17 ST
"0
187
640 CO
�28
2
-- W17)
F4,'
j 187-
0
648
ME is ST I j
Wa[er and i(clwer Depa 1 -I'm e[d,
WAT1,',R Mk.ts — F13
'M
1, il
LEGEND
water Main ftaw Water man
II'dVatWOOteruf1w Sludge: tine
M Vlvt
calcium C*bwala we casing
MunidfW BoundW BloCkS
Twsmizion Main
Low Prmure Mafn
Culvert
% V / Section Boundary
Marker Symbols
now mew
Sludge Lagoon
Iii
C:
,1 1 Treatment Plant Connedon No*
Attachment D
Pump Station Monthly Information
Sanitary Sewer Pump Stations Database
Pump Station Monthly Information
Pump Station: 30 - 0002
UNINCORPORATED DADE GOUNIN
925 BISCAYNE BLVD
Moratorium: OK
OK
Moratorium in effect since: 1/27/2007
Section -Township - Range: 31 53] 42]
-F -F
Generator: FYI Telemetry: FYI ET Clock: Eyl
Type:. Class: Fml Speed: Fv I H.P.: 1-11
Peak Factor (last 7 entries): 2.40 Number of Pumps: 5
Yearly NAPOT (hrs): 178
2;40 'TRANSFER 01/27/2007
Reserved Flow (gpd): 3;166,202
Projected Napot (hrs): 5.98
Used Capacity (%): 59.80
Station Gross Capacity (gpd): 57,600,000
Station Reduction Factor: 0.60
Station Net Cap Certified (gpd): 0
Station Net Capacity (gpd): 34,560,000
Indicated Flow (gpd): 5,443,200
Gc�,—,erated: 7/2/2007 - 08:34 AM Page 1 of 1
14.72
2
5
13ROD..§R
12/2112006:
10N/2.006.
4,17
16!67
Y
5
BRQD,8k
11/22!2006:
. . ....... ...
.61.2 17 2QQ&
C20
16;*80
Y
5
BRODSR
.1012012006.
8 . 28/2006
3.761
15.04
Y
5
BRODSR
026/2066
7128120.06
3.72
14;89
Y
5
CORRECTED ENTRY RN 9/2.7/06 NEWAR
08/22/2.006
Gc�,—,erated: 7/2/2007 - 08:34 AM Page 1 of 1
Kimley Horn was retained to perform a limited Site Utility Study and performed only those tasks
specifically stated in our scope of services. The Client may use this report as part of its due
diligence, but this report should not be used as the sole basis for the Client's decision making.
We endeavored to research site development issues and constraints to the extent practical given
the limited scope, budget, and schedule agreed to with the Client. Our assessment is based in
large part on information provided to us by others (city staff, DOT staff, Utility Company
Representatives, etc) and therefore is only as accurate and complete as the information provided
to us.
This report is based on our knowledge as of July 2, 2007. New issues may arise during
runfodevelopment because of changes in governmental rules and policy, changed circumstances, o.-
unforeseen
reseen conditions. Our assessment is based on the desires of the Client that have been
specifically disclosed to us. The Client should do its own due diligence to become comfortable
with our findings and to be sure no other significant development issues exist.
Major Use Special Permit Site Utility Study
Royal Atlantic, Tract "A ", Sportman Park, Section `A "
City of Miami, Florida
Page 13